Product Evaluation Report of

Jeld-Wen Inc. Steel Wood Edge Impact Glazed & Opaque Outswing Door

Report No. 1478 Florida Building Code 2007

Category: Sub – Category: Product: Material: Product Dimensions:

Exterior Doors Swinging Exterior Door Assemblies Steel Wood Edge Impact Glazed OS Door Wood/24 Ga. Steel 37.50” x 81.75”

Prepared For: Jeld-Wen Inc. 3737 Lakeport Blvd. Klamath Falls, OR. 97601

Digitally signed by Alex Spyrou Reason: I am approving this document Date: 2011.09.09 13:45:32 -04'00'

 

Prepared by: Alexis Spyrou, P.E. Florida Professional Engineer # 68101 Date: 8/18/2011 Contents: Evaluation Report Pages 1 – 4 Installation Details Pages 5

 

Alexis Spyrou, P.E.  Florida No. 68101 

BUILDING DROPS

FL#: Date: 8/18/2011 Report No: 1478

A Perfect Solution in Every Drop  Certificate of Authorization: 29578 

  Manufacturer:        Product Category:      Product Sub‐Category:      Product Name:              

Jeld‐Wen Inc.  Exterior Doors  Swinging Exterior Door Assemblies  Steel Wood Edge Impact Glazed & Opaque Outswing Door  (Impact)  37.50” x 81.75”           

 

 

  Scope:   

This is a Product Evaluation Report issued by Alexis Spyrou, P.E. (FL # 68101) for Jeld‐Wen Inc.   Alexis Spyrou, P.E. does not have nor will acquire financial interest in the company manufacturing or  distributing the product or in any other entity involved in the approval process of the product named  herein. 

  This product has been evaluated for use in locations adhering to the 2007 Florida Building Code.    See Installation Instructions JW152011FL, signed and sealed by Alexis Spyrou, P.E. (FL # 68101) for  specific use parameters.        Limits of Use:    1.    2.  3. 

4.  5. 

This product has been evaluated and is in compliance with the 2007 Florida Building Code,  including the “High Velocity Hurricane Zone” (HVHZ).  Product anchors shall be as listed and spaced as shown on details.  Anchor embedment into  substrate material shall be beyond wall dressing or stucco.  When used in areas requiring wind borne debris protection this product complies with  Section 1609.1.2 of the 2007 Florida Building Code and does not require an impact resistant  covering.    Site conditions that deviate from the details of drawing JW152011FL require further  engineering analysis by a licensed engineer or registered architect.  See Installation Instructions JW152011FL for size and design pressure limitations. 

             

 

 

Alexis Spyrou, P.E.  Florida No. 68101  Page 2 of 5   

BUILDING DROPS

FL#: Date: 8/18/2011 Report No: 1478

A Perfect Solution in Every Drop  Certificate of Authorization: 29578 

  Quality Assurance: 

    Performance Standards: 

The manufacturer has demonstrated compliance of door products in Accordance  with the Florida Building Code for manufacturing under a quality assurance program  audited by an approved quality assurance entity through National Accreditation &  Management Institute, Inc. (FBC Organization #QUA1789) 

The product described herein has been tested per:         

TAS 201‐94  TAS 202‐94  TAS 203‐94  ASTM E 330‐02  ASTM E 283‐91  ASTM E 331‐00  ASTM E 1886‐05  ASTM E 1996‐05 

  Referenced Data:    Reports to qualify use of Steel Wood Edge Doors:            1.  Product Testing performed by National Certified Testing Laboratory, Inc.  Report #: NCTL‐210‐3195‐1,   Report Date: 09/28/2005  Report #: NCTL‐210‐3195‐1A,   Report Date: 09/28/2005    2.  Product Testing performed by Quality Testing, Inc.  Report #: SJW2009‐200,   Report Date: 01/18/2010    3.  Product Testing performed by Certified Testing Laboratories  Report #: CTLA718W,     Report Date: 11/18/2001    4.  Quality Assurance    National Accreditation and Management Institute    (FBC Organization #: QUA 1789)      Miami Dade BCCO    (FBC Organization #: CER 1592)    NOA #: 08‐0206.01     Products described herein are tested in accordance with standards listed above as required by the 2007 Florida  Building Code and do not require an impact resistant covering.         

 

Alexis Spyrou, P.E.  Florida No. 68101  Page 3 of 5   

BUILDING DROPS

FL#: Date: 8/18/2011 Report No: 1478

A Perfect Solution in Every Drop  Certificate of Authorization: 29578 

    Installation:   

1.   Approved anchor types and substrates are as follows:  Through Frame Installation:  A. For 2x wood buck substrate, use #10 Wood Screw type installation anchors of sufficient  length to achieve a minimum embedment of 1.50” into the wood substrate.    B. For concrete or masonry substrate where one by (1X), non‐structural, wood bucking is  employed, use 3/16” diameter ITW Tapcon type concrete screw anchors of sufficient  length to achieve minimum embedment of 1.25” into concrete or masonry. 

  C. For concrete or masonry substrate where wood bucking is NOT employed, use 3/16”  diameter ITW Tapcon type concrete screw anchors of sufficient length to achieve  minimum embedment of 1.25” into concrete or masonry.    Refer to Installation Instructions (JW152011FL) for anchor spacing and more details of the  installation requirements.    Design Pressure: 

  Design Pressure  Positive  Negative 

             

 

 

60 PSF  60 PSF 

 

                     

 

 

Alexis Spyrou, P.E.  Florida No. 68101  Page 4 of 5   

BUILDING DROPS

FL#: Date: 8/18/2011 Report No: 1478

A Perfect Solution in Every Drop  Certificate of Authorization: 29578 

   

Installation Method Jeld-Wen Inc. Steel Wood Edge Impact Glazed & Opaque Outswing Door  

37 1/2" O.A. FRAME SIZE

11 1/2" TYP.

6" TYP.

3" TYP.



6" TYP.

OUTSWING: 81 3/4" O.A. FRAME SIZE

3" TYP.

10 1/2" TYP.

 

 

 

Alexis Spyrou, P.E.  Florida No. 68101  Page 5 of 5