Instruction Leaflet K1005V3
Instruction Manual - K1005V3 June 2015
June 2015
Solstar LED
For Emergency Fittings Only
Solstar LED
IP20
IP40
Fit LED into plastic shroud
Install into cutout in ceiling next to luminaire
Product luminaires comply with EN60598 and are suitable for use in normal interior o conditions. o o
o
This luminaire has an ambient temperature range of -20C to +25C for the non-emergency version Standard versions are Class II double insulated, emergency versions are Class I and must be earthed
Charge Indictor LED
Luminaire Head IP40 rated, Gearbox IP20 rated For Emergency variants - This luminaire has an ambient temperature range of +5C to +25C, to ensure
the batteries work correctly 50/60Hz supply.
Suitable for 220-240
1
ENSURE MAINS SUPPLY IS SWITCHED OFF Cut aperture and feed mains cable through, wire driver/gearbox as per diagram to the right
Wire mains cable into driver: Neutral - Blue Live - Brown
High Frequency Incoming Mains Cable into driver
To Downlight
LIVE NEUTRAL
DALI Wiring Incoming Mains Cable into driver LED OUTPUT
LIVE NEUTRAL
+ -
Small
Max. 155.0mm
Large
Max. 205.0mm
To Downlight
DA DA ISOLATED DALI INTERFACE
Feed driver/gearbox through aperture to sit in ceiling
DALI BUS
For emergency - open gear box and wire terminal block as per label. Live (Unswitched) (Black) Live (Switched) (Brown) Earth (Green/Yellow) Neutral (Blue) EMERGENCY LUMINAIRE MUST BE EARTHED LUMINAIRES MUST NOT BE MEGGER OR HIGH VOLTAGE TESTED
3
2
Insert fitting into aperture, tighten 3 x screws to rotate bearer arms out and draw up the fitting
b
Max. 150.0mm
Max. 25.0mm
Note: Haloglass attachment is fixed on using the same method replacing the standard bezel
Safe Operation 1. Check the rating label for voltage and frequency before connecting this luminaire to the electrical supply. 2. Ensure that the mains supply is switched off when working on this luminaire, whether installing or carrying out any other servicing. 3. Do not mount luminaire on or close to readily flammable materials. Minimum clearance 50mm 4. To prevent damage to driver, do not mix with conventional magnetic ballasts on the same electrical circuit. 5. Where use in more onerous situations is required, e.g. In part-completed buildings before “drying-out” is completed, or areas where ambient temperatures are outside the normal temperature range, then consult our Sales Office. 6. The light source contained in this luminaire shall only be replaced but the manufacturer, his service agent or a similar qualified person. Servicing and Disposal 1. At commissioning and handing over of installation ensure that a copy of these instructions is presented to the authority responsible for the operation and maintenance of the luminaries. 2. Servicing, e.g. cleaning, must only be carried out after the electricity supply has been switched off. It must not be assumed that luminaries with lamps not lit are switched off-always check before servicing. 3. Cleaning should be carried out at regular intervals to ensure that dirt does not accumulate to an extent that will impair the thermal safety or optical performance of the luminaire. Regular cleaning will also ensure that the optical performance of the luminaries is maintained. 4. Avoid touching the LED array surface. To clean - Blow surface with either dry air or nitrogen gas. 5. At the end of life the luminaire is classed as WEEE under directive 2002/96/EC and should be disposed of in accordance with local legislation.
Luminaire Servicing
Luminaire Cleaning
a) Twist and remove bezel from fitting
End of Life and Components Disposal
a
b) Lift fitting to aperature and connect plug and socket between fitting and driver together
WEEE
Once secure, line up the arrow on the bezel with the arrow on the fitting, fit together and rotate the direction of the arrow until bezel engages with the springs
Eaton Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB Sales
General
International Sales
T: +44 (0)1302 303303 F: +44 (0)1302 367155 E:
[email protected]
+44 (0)1302 321541 +44 (0)1302 303220
[email protected]
+44 (0)1302 303250 +44 (0)1302 303251
[email protected]
K1005V3